< Previous

VARIO pluggable cartridge for neutral protection GT range without integrated disconnector

Reference : VARKNGT - Code : 070510

TYPE 2

Technical specifications

Voltage protection level Up 1,3/1,5 kV
Nominal discharge current 8/20 waveform In 15 kA
Nominal voltage level Un 230/400 Vac
Maximal steady-state voltage Uc 275 V
Maximal discharge current Imax 40 kA
Earthing system TT/TN
Testing standards NF EN 61643-11 / Type 2
Dimensions (mm) 1 mod
VARIO pluggable spare cartridge, Uc 275V, Imax 85kA, In 20kA, Up=1.8kV for neutral in the GT SPD range without disconnector with or without remote status signal contact

Back to the product list